Skip to content

Note

What Niagara does with the Modbus address you type

A Modbus point that reads a completely unrelated register is usually not a wiring fault. The address field holds a format and a string, and the format it starts on is not the one the vendor document is written in.

  • Modbus
  • Integration
  • Station engineering

Written

The field is not a number

The address on a Modbus proxy extension is a small component of its own. It carries two properties: an address format — one of hex, decimal or modbus — and the address itself, stored as a string. Nothing is decided until the driver reads both together.

The format a fresh address starts on is hex. So typing 40001 into a point whose format has not been changed asks for data address 0x40001, which is 262145. Validation does not stop it either: in hex mode the only check is that the parsed value is not negative. The point is accepted, the device answers with an exception or with something else entirely, and the argument on site is about the device.

What each format does to the number

FormatParsed asSent as the data address
hex (default)base 16the value, unchanged
decimalbase 10the value, unchanged
modbusbase 10the value with its group prefix removed

Only the third one does the subtraction that vendor documentation assumes. In modbus format the driver strips the prefix in a fixed order: above 40000 it subtracts 40001, above 30000 it subtracts 30001, above 20000 it subtracts 20001, above 10000 it subtracts 10001, and otherwise it subtracts 1. That is the off-by-one, done for you — but only in that one format.

Hex and decimal both hand the number to the wire as it stands. They are the right choice when a vendor publishes true zero-based data addresses, which some do, and the wrong choice for any document written in the five-digit convention.

The boundary values fall through

Each of those tests is a strict greater-than. So 40000 is not above 40000, drops to the next test, is above 30000, and comes out as data address 9999 — an input-register offset, from an address that reads like a holding register. The separate check that decides which register group an address belongs to wants above 40000 for holding and above 30000 but below 40000 for input, so 40000 belongs to neither group.

The same gap exists at 30000, 20000, 10000 and 0. In the five-digit convention none of those is a legal address — every group starts at x0001 — so this is only reachable from a typo or from a generated point list that is one out. It is worth knowing because nothing reports it. There is no fault and no warning; the point simply reads a different register.

The 2xxxx range is accepted. In modbus format an address is considered valid anywhere from 0 to 49999, and 20001 upwards is mapped by subtracting 20001. Very few devices publish anything in that range, so an address that lands there is almost always a mistyped 30000-series address that has been quietly accepted.

Nine data types, and the default is unsigned

The data type is a separate decision from the address, and it settles two things at once: how many consecutive registers the point reads, and how the bits are interpreted.

Data typeRegistersSigned
Integer (default)1no
Signed integer1yes
Long2yes
Unsigned long2no
Float2—
Unsigned 48-bit long3no
Double4—
Signed 64-bit long4yes
Unsigned 64-bit long4no

A point left on the default reads one register, unsigned. A flow or outside-air temperature published as tenths of a degree then reads 65506 at −3.0 °C rather than −30, and the trend looks like a sensor that fails in cold weather. Anything that can go negative needs the signed type chosen explicitly.

The register count also matters for how the point is grouped. A four-register double starting one register before the end of a contiguous block quietly reaches into whatever follows it.

Three byte orders for 32 bits, and one arrangement is missing

For two-register values the driver offers exactly three arrangements — 1032, 3210 and 0123. The float and long properties both default to 3210; 1032 is only the enum's own zero ordinal, which is the trap — it is what a decompiler shows first and it is not what a new point gets. The fourth possible arrangement, 2301, is not on the list. A device that publishes its 32-bit values that way cannot be read correctly by setting a property: the practical answer is to read the two registers as separate 16-bit points and combine them in logic, or to have the device's own word order changed where its configuration allows it.

Values of four registers get eight arrangements rather than three, defaulting to 76543210. Meters that publish 64-bit energy totals are the common case, and the default is the one most of them use.

The order to change things in

When a value is wrong, these are three independent choices and changing them at random turns a five-minute fix into an afternoon. Work through them in order:

  • Address format first. It decides what the string you typed even means, and it is a property of each address rather than of the device.
  • Then the data type. A value that is plausible but negative-looking, or that is roughly right but jumps to 65535, is a sign or width problem.
  • Then the byte order. A value that is nonsense by orders of magnitude, on a point that reads two or four registers, is word order.

The companion note on Modbus register addressing covers the conventions themselves and why a vendor document and a register map disagree, and poll scheduling and busy time covers what happens once the points are right and there are a lot of them. Where a map has to be read properly before any of this, protocol integration is that work, and station engineering is the station around it.

Sources

Where this is written down

Related

Where this comes up in the work

More notes

Other things worth writing down

Next step

Tell us the version, the hardware, and what it has to do.

You will get a written scope back, and a clear answer on whether we are the right team for it. If the honest answer is that you do not need us, you will get that instead.