Note
What Java 25 does to Niagara's module permission model
A module asks for privilege in its manifest, and the framework grants or refuses it through Java's Policy and SecurityManager. On a Java 25 JVM neither can be installed — so those checks do not start failing. They stop happening.
- Module development
- Station security
- Migration
How a module asks for privilege today
Niagara 4 has a real, documented privilege model for module code, and most people who write modules have never had to look at it, because the framework asks for the permissions on their behalf. Tridium's developer documentation describes it plainly: Niagara 4 introduced the use of Java's Security Manager to restrict who may run certain sections of code, and from 4.2 onward the policy is determined by the contents of a module's own manifest, in which a module requests the permissions it needs.
Read off the bytecode, the machinery is a custom java.security.Policy
subclass installed by the runtime environment, plus a hierarchy of permission-group
classes in the core framework jar. There are 27 named permission groups a
module may request — counted off the registration map in the factory class, and
matched one to one against the group implementation classes beside it. The names are a
reasonable index of what a module can do that matters: authentication, unauthenticated
access, backups, key store, loading libraries, reflection, network communication,
modifying IO streams, managing execution, shutdown hooks, setting system time, system
properties, signing, HSM signing, reading environment variables, database connections,
MBean access, protection domain, access class, third-party permission, managing server
trust anchors, cloud bearer token, renaming and restarting the station, runtime
execution, diagnostics, logging and UI.
Six of those groups — access class, HSM signing, MBean, protection domain, reflection and third-party permission — require the module to be signed before the request is honoured at all, each of them overriding the base class to say so. That detail matters later.
What a Java 25 JVM does to that machinery
The Security Manager was deprecated for removal, then permanently disabled. On a current JVM the relevant calls behave like this — measured by running them, not read off a release note:
| Call | What it does on Java 25 |
|---|---|
| System.getSecurityManager() | Returns null. Always, with no way to change it. |
| System.setSecurityManager(sm) | Throws UnsupportedOperationException — including when the
argument is null, so even code whose only intent is to
disable the manager now throws. |
| Policy.setPolicy(p) | Throws UnsupportedOperationException. A custom
Policy can be written, compiled and shipped; it can never be
installed. |
| AccessController.doPrivileged(a) | Runs the action. It does not elevate anything, because there is no longer anything to elevate past. |
| Subject.getSubject(context) | Throws UnsupportedOperationException. |
| Subject.current() | Works. This is the replacement, and it sees a subject established by either
the old doAs or the new callAs. |
So the permission model has no JDK left to stand on. Not "needs porting" — the two entry points it is built on both throw.
The checks do not fail, they disappear
This is the part worth being precise about, because it is the opposite of what a
removal usually does. The framework-wide idiom at a check site is: fetch the
security manager, and if it is not null, ask it to check a permission. On Java 8 the
manager is there and the check runs. On Java 25 the manager is null, the
if is false, and execution continues straight past into the guarded
work.
Scanning the 4.15 module set on disk, 29 stock modules carry that
pattern — a class that fetches the manager, null-checks it and then
calls one of its check methods. Two more fetch it and null-check it
without going on to a permission check, which is why a looser sweep reports 31. The
29 read like an index of the security surface: the core
framework jar, the platform layer, platform crypto, the signing service, client
certificate authentication, SAML, the web and servlet layers, fox, tunnelling,
backup, the cloud connectors, email, the OPC UA server, the system database, the
HTTP client, and Workbench itself. Four representative examples, decompiled, guard
platform initialisation, the station's signing password, the signing service, and
the station's password-encryption key.
The code still runs. The permission layer is simply not there. A module that would have been refused a permission is not refused; nothing logs, and nothing looks broken.
To be clear about what this is and is not: this is not a live hole in anything shipping today. Niagara 4 runs on Java 8, where the layer works exactly as documented. It is a statement about what has to be rebuilt before the framework runs on a modern JVM — and rebuilding it is the framework vendor's work, not a module author's.
Two places where it is worse than a no-op
A silently-skipped check at least keeps running. Two calls in the framework's own core do not: they throw where they used to return.
Both are the same call — reading the authenticated subject off the access control context. One is in the runtime environment's security utility class. The other is the core framework's session manager, in the method that answers "who is the current user". Its blast radius is the whole web and UI session stack: the web and servlet layers, bajaux, the legacy HX views, the HTTP client, backup views.
And it is documented public API for module developers. The developer documentation's own guidance on CSRF protection tells you to fetch the current session and read its CSRF token off it. Any third-party module that followed that advice throws on a Java 25 JVM — not because the module is badly written, but because it did what the documentation said.
The fix is mechanical: Subject.current() replaces
Subject.getSubject(...) and works under both the old and the new
scoping calls. But it is a one-line fix inside the framework's own jars, so
no amount of work on a third-party module makes that call site safe. Everybody waits
on the same edit.
What this means if you write modules
Four practical consequences, in the order they are likely to bite.
The documented way to request privilege has no announced replacement. The published breaking-change material for the next major version says, on this subject, that the Security Manager is removed. It does not say what a module uses instead to request a permission, or what happens to a manifest that asks for one. That is the single biggest open question for anyone maintaining a module catalogue, and it is not answerable from public material.
Do not build new work on it. If a design depends on being granted a
permission group, or on doPrivileged actually elevating, it depends on a
mechanism with no forward path. A module that needs no permission group at all has
one fewer unknown in it, and in practice a module that sticks to the old, stable part
of the component and driver API needs none.
Two specific calls to stop writing now. Reading the subject off the access control context, and the session manager call above. Both have replacements that already work on Java 8, so moving off them costs nothing and removes a guaranteed failure later. Likewise, the old subject-scoping call still works but is deprecated for removal; the newer one is a drop-in.
A guess, labelled as one. Six permission groups already require a signed module, and the next major version makes a valid signature mandatory for every module. The most likely shape of the replacement is therefore signature-at-load-time rather than permission-at-call-time. That is inference, not information. The measured part is only that the current mechanism cannot work.
How this was measured, so you can repeat it
No licence and no pre-release access is involved, which is the point. A Niagara licence gates running Workbench and a station. It does not gate reading a jar that is already on your disk, and it does not gate running a JDK.
Three steps.
- Put a real Java 25 JDK next to the install. Not as a runtime for Niagara — nothing runs on it. It is there to be asked questions.
- Ask it what each API actually does. A short program that calls every API in question inside its own try/catch and prints the outcome, plus a second one that simply asks whether each package still resolves. That output is the evidence; the rule table is written from it.
- Read the jars' constant pools. Every class records the types and members it links against. Walk them and you get, per module, the exact list of removed or changed APIs it touches — then confirm each hit at the call site with a decompiler before believing it.
Why the third step needs the second. The first pass of this scan produced five blockers. Three were wrong because the rules came from release notes rather than from the JVM, and two more were wrong because a reference in a constant pool is not a call that ever runs. Running a real JDK and a decompiler removed all five. A finding that has not survived both steps is a guess with a severity label on it.
What to ask the Developer Program
If you hold a developer membership, these are the questions whose answers are not in public material, and they are worth asking in writing:
- What replaces a module's permission request? Is the manifest element retained, ignored, or an error?
- Are the 27 permission groups enforced by any other mechanism, or is module code now simply trusted once its signature verifies?
- Has the session-manager call that reads the current user been changed to the supported replacement, and in which pre-release build?
- Is there a supported way for a module to learn the authenticated user, given the old route throws?
- Does the documentation that tells module authors to use that call get updated, and when?
What this does and does not prove
Measured. What a Java 25 JVM does to each API, by running it. Which modules in the 4.15 set on disk touch those APIs, by reading their bytecode. That the permission model's two installation points both throw.
Not measured, and not claimable. Anything about how the next major version actually behaves. No Niagara 5 build exists to test against — pre-release access runs through the vendor's own programme and there is no public download — so every statement here is static analysis against a Java 25 JDK, not a test on a Niagara 5 build. It says nothing about API changes, manifest schema changes, or repackaging done for other reasons. A module that passes a scan like this can still fail to compile against a new SDK.
That is a narrower claim than "N5-ready", and it is the one that can be backed up.
The companion note covers what a scan like this finds across a real module set, and what it cannot tell you: what an N5 module scan actually finds. For the audit and porting work itself, see Niagara 5 migration.
Sources
Where this is written down
- JEP 486: Permanently Disable the Security Manager — The change this note is about, in the words of the people who made it: enabling the Security Manager is an error the JVM refuses to start on, and System.setSecurityManager throws. Delivered in JDK 24, so 25 inherits it
- JEP 411: Deprecate the Security Manager for Removal — Where the deprecation started, and the reasoning the permission model Niagara built on was already being argued against
Related
Where this comes up in the work
Niagara 5 migration
Niagara 5 readiness audits and migration, including JACE 8000 to JACE 9000: which third-party modules survive the new runtime and mandatory signing.
Custom modules & drivers
Bespoke Niagara rt, wb and ux modules and drivers written against the Baja API: pure Java, signed, and stamped to install across a mixed estate.
More notes
Other things worth writing down
What happens to third-party modules moving from N4 to N5
A module with no Niagara 5 build can stop the migrator outright, and one that has a build can still fail to load. What breaks, and why.
- Migration
- Estate management
- Module development
What a static Niagara 5 module scan actually finds
Reading a module's bytecode against Java 25 gives a per-module answer. What it finds, what it cannot tell you, and the false alarms it avoids.
- Migration
- Module development
- Estate management
What actually blocks an AX to N4 migration
A station cannot migrate until every module it uses has been refactored for Niagara 4 — and licences, users and permissions all change shape on the way.