Doing one thing to fifty stations at once
Fifty controllers means fifty platform connections, or one provisioning job. The job is repeatable, schedulable and logged; the fifty connections are an afternoon nobody records.
- Provisioning
- Estate management
- Supervisor
What it replaces
Provisioning is a licensed feature of a station running on a Supervisor. It automates tasks on the remote hosts in that station's NiagaraNetwork — and these are mostly platform tasks, the kind that would otherwise mean opening a platform connection to each host in turn, or tunnelling to it.
Two consequences follow, and the second one is easy to miss.
- You need one station connection to the Supervisor and nothing else. The job runs from wherever you can reach that station.
- That includes a web browser. Ordinary platform tasks cannot be done from Web Workbench at all — provisioning is the exception, because the Supervisor is doing the platform work, not your client.
Two kinds of job
The distinction matters because only one of them is suitable for anything recurring.
- A one-shot job, built in the Niagara Network Job Builder —
the default view of the
ProvisioningNwExtunder the NiagaraNetwork. Right for a software rollout you are performing once, now. - A prototype job, a
NiagaraNetworkJobPrototypefrom the palette, which is reusable and can be linked to a trigger schedule. Right for anything periodic, and it can still be run on demand.
Adding the network extension also creates a set of provisioning device extensions under every Niagara station in the network automatically, including stations added later.
What actually happens when a job runs
Reading the execution order once saves a lot of confusion later, because the step count on the progress bar moves while you watch it.
- Adjacent software-install, file-copy and upgrade steps are combined before execution, to avoid repeating dependency checks and to minimise reboots.
- If the job includes a licence update it runs first and once, as a single silent enquiry to the licensing server covering every host in the job.
- The remaining steps then run sequentially per station, working down the station list. A station reports Running, then Success or Failed.
- A failed step ends that station — no further steps run on it — and the job moves to the next one. The job as a whole reports Failed if even one step failed anywhere.
- Cancelling marks the current station and every station after it as Canceled.
The total step count changes mid-run because of that step combination, the licence step being created automatically, and the steps skipped after a failure. It is not a bug and it is not a progress bar worth staring at.
From Niagara 4.7 jobs can run in parallel across stations. The maximum is ten; the
practical minimum follows the Supervisor's core count, and the ceiling is set by
Max Provisioning Threads on the batch job service.
The backup action almost everybody uses first
The NiagaraNetwork has a Start Backup action that backs up every station. On a site with four controllers it is fine. Tridium's own documentation recommends against it as soon as the estate grows, for three reasons.
- It builds one enormous job that can take a very long time.
- It loads the whole system at whatever moment somebody happened to click it, which is usually during the working day.
- The files it leaves behind are not governed by any retention policy. They accumulate on the Supervisor until a human deletes them, and the eventual symptom is a full disk.
The recommended shape instead. Several job prototypes, each covering a subset of stations, each linked to its own trigger schedule, staggered — ten minutes apart is the documented example — and run out of hours. Each prototype then has its own retention policy, which is the part the action cannot give you.
Retention, because jobs keep files
Provisioning persists everything by default: who submitted the job, when it started and ended, the detail of each step and its log output. For backup jobs the saved distribution file is kept too, and can be restored straight from the step log, which launches another provisioning job to do it.
That persistence is the feature and the risk. Each job prototype carries a retention policy with three shapes:
| Policy | Behaviour |
|---|---|
| Retain permanently | Nothing is ever deleted automatically. Appropriate for a one-off migration record, wrong for a nightly backup. |
| Dispose after a period | Deleted relative to the job's end time. Defaults to seven days. |
| Keep a number of executions | Keeps the most recent n. By default it counts only successful runs — clear the checkbox and failures count too, which changes how far back your retained history actually reaches. |
A separate enforcement frequency, one hour by default, decides how often the policy is applied, and there is an action to enforce it immediately. Disposing of a job deletes its files as well as its record — including the backup distribution file, so "tidying up the job list" is not a cosmetic operation.
Two things to check before relying on it
Jobs can raise an alarm on failure, on success, or both. Configure failure alarms at minimum, or an unattended nightly job is only as reliable as somebody's habit of looking at a list.
And mixed estates need care: where AX-3.8 hosts share a network with Niagara 4 ones, limitations apply, largely from the security changes in N4, and job steps introduced in later versions are not always backward compatible. A provisioning job that works across the new half of the estate is not evidence that it works across the old half.
What to set up on a Supervisor
- The network extension, so every station gets its provisioning extensions without anyone remembering to add them.
- Backup prototypes in groups, staggered, out of hours, each with a retention policy that matches the disk you actually have.
- Failure alarms routed to somebody who reads them.
- One restore, proved, from a job step log onto spare hardware — the only evidence that any of this worked.
- A note of the parallel thread count you settled on, and why, so the next person does not raise it to ten on a small Supervisor.
Related
Where this comes up in the work
Workbench tooling
Custom Workbench views and tools for repetitive Niagara work: bulk renaming and retagging, station audits, provisioning helpers and module inventories.
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
More notes
Other things worth writing down
Scheduled station backups, and the gap
A Supervisor can back up every station in its Niagara Network on a schedule. The station it does not cover that way is its own.
- Backups
- Provisioning
- Supervisor
When a third-party module's vendor no longer exists
The Marketplace storefront is gone and vendors are winding down. How to list which third-party modules a station depends on, and who owns each.
- Migration
- Estate management
- Drivers
What a static Niagara 5 module scan actually finds
Reading a module's bytecode against Java 25 gives a per-module answer. What it finds, what it cannot tell you, and the false alarms it avoids.
- Migration
- Module development
- Estate management