Niagara does not grant permissions to people. It grants a level of access to a category of objects, to a role, which a person then holds. Every confusing symptom comes from one of those four words.
- Station security
- Permissions
- Commissioning
The four things, in order
Access control in a Niagara station is a chain, and you cannot reason about any one link without the others.
- Every component belongs to at least one category.
- Every slot has a permission level — operator or admin.
- A role holds a permissions map: for each category, what rights it grants at each level.
- A user is assigned one or more roles, and their permissions are the union of them.
Rights themselves are three: read, write, and invoke an action. They apply to component slots, folders, files and histories alike.
A category mask is a hex string, and the highest index sets its length
A new station arrives with two basic categories: User (category 1) and Admin (category 2). Everything lands in User except three services — the user service, the category service and the program service — and the entire file space, which go to Admin.
Categories can also be inherited from a parent rather than explicitly assigned, and the two mechanisms can be mixed. What cannot happen is a component in no category at all.
Every component carries a category mask, and it is not a byte array.
BCategoryMask holds a hex string: one hex character per four
categories, so size() is the string length times four, and
get(n) divides n-1 by four to find its character.
The masks are interned in a static cache and a component's slot map holds a
reference to a shared instance — two of them, the assigned mask and the
inherited one — so adding a category lengthens a shared string rather than
fattening every component in memory. Where the length is paid per component is
encoding: the mask goes out through writeUTF, so every four categories
adds a character to what each component writes on a sync or into a backup.
The practical advice does not change, but the reason does. The string is sized from
the highest index in use, not the number of categories in use —
make(int[]) sizes the buffer as max((i-1)/4)+1. Deleting
category 40 and leaving 41 in place shortens nothing. Keep the count low and the
indexes contiguous.
Beyond that, how you group is a modelling decision: by equipment type — lighting, door access, HVAC — or by geography, floor by floor. Which one is right depends entirely on how the roles will be drawn, so decide the roles first.
Operator and admin are a property of the slot
This is the part that is genuinely unintuitive. The operator/admin distinction is not a property of the user or the role — it is a config flag on the slot. If a slot's Operator flag is set, the slot is at operator level. If it is cleared, the slot is at admin level.
Most slots default to admin level. The notable exception is the out
slot, which is normally operator level — which is exactly why an operator can
watch a value without being able to touch the logic that produces it.
Admin level carries more than write access to values: it lets a user see and change the slot flags themselves on the slot sheet. Granting admin rights broadly hands out the ability to reconfigure the permission model.
The permissions map
Editing a role opens a grid with one row per category and columns for the operator
and admin levels. Rights are written in a shorthand worth reading fluently: lower
case for operator level, upper case for admin. r is operator read,
rw operator read and write, rR adds admin read, and
rwRW is full rights at both levels.
A super user sidesteps all of it — every permission, every category, every object — and can create further super users. Ordinary users cannot grant what they do not hold, so a non-super user cannot promote anybody to super user.
Two symptoms that account for most of the calls
"User does not have access to station. Check permissions." The credentials were correct — that is the point of the message. Either no role is assigned to the user, or the roles they hold grant nothing. A role needs permissions on at least one component before the user can enter the station at all.
The second is users who cannot change their own password, and the fix is specific. The user service has its own permission scheme, unlike every other component:
| Slot level | Role grants | The user can |
|---|---|---|
| Operator | r |
Read their own account's properties. Other users are hidden. |
| Operator | rw |
Read and write their own account — this is the setting that lets somebody change their own password. Other users still hidden. |
| Admin | rR |
Read every user's properties. |
| Admin | rwRW |
Read and write all non-super users, add and delete users, and use the User Manager and Permissions Browser. |
So: leave the Authenticator slot at operator level, which is its default, and give every non-super-user role operator-level write on the category holding the user service. By default the new station wizard puts that service in the Admin category, which is why the permission people want is in a place they do not think to look.
Ancestors are granted automatically
Giving somebody access to a point buried six levels deep would be useless if they could not see the folders above it. The station handles this: it automatically grants operator-level read on every ancestor of a component a user can reach, so the nav tree is navigable.
It does so periodically rather than instantly, which is why a freshly granted permission sometimes appears not to work. The category service has an Update action that forces it.
Files have their own rules
The whole file space defaults to the Admin category, and file permissions behave mostly at operator level.
- Operator read to view a file; operator write to edit one.
- Operator read on a folder to list it and copy children out; operator write to create or delete children.
- A few views want admin-level write — the nav file editor among them.
- Operators typically need operator-level read on the standard folders: nav, px, images, html.
Some rules are not yours to set. System module files are automatically restricted to
operator-level read. Non-super users are denied everything outside the station home
directory. A Supervisor's provisioning folder needs admin-level read to be visible
at all. And the station's own config.bog and its backup are not
accessible in the file space to anybody, super user included.
Do not solve a file-access problem by granting Admin. The documented advice, and the right one, is to create a new category containing only what that person needs. Raising somebody to Admin to let them open one folder grants them the three services and the whole file space as well.
A model that survives handover
- Write the roles down first — duty by duty, not person by person. Categories follow from roles; roles do not follow from categories.
- Keep the category count small and contiguous. Every one of them is bytes on every component.
- Give every non-super role operator write on the user service category, so password changes are self-service on day one.
- Log in as each role and try to break it. The category browser tells you what a role can reach; actually logging in tells you what it feels like.
- Count the super users before handover, and again after. The number should be small and deliberate.
Related
Where this comes up in the work
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
Workbench tooling
Custom Workbench views and tools for repetitive Niagara work: bulk renaming and retagging, station audits, provisioning helpers and module inventories.
More notes
Other things worth writing down
The certificate on a new JACE
Every station starts with a self-signed certificate it generated itself. What that is good for, what it is not, and what breaks on the day it expires.
- TLS
- Certificates
- Commissioning
What actually blocks an AX to N4 migration
A station cannot migrate until every module it uses has been refactored for Niagara 4 — and licences, users and permissions all change shape on the way.
- Migration
- Estate management
- Module development
When the document and the code disagree
The method behind a protocol-discrepancy audit: treat a documented default, range or address as a claim, then settle it against the code, twice.
- Modbus
- BACnet
- Integration
- Commissioning
Next step
Tell us the version, the hardware, and what it has to do.
You will get a written scope back, and a clear answer on whether we are the right team for it. If the honest answer is that you do not need us, you will get that instead.