Note
Tags, dictionaries and the licence you need
Tagging is sold as tidiness. It is not: it is the difference between a station another tool can read and one it can only display.
- Tagging
- Data modelling
- Haystack
Check the licence first. The tags licence feature is
required to use the TagDictionaryService and tag dictionaries on a
station. A tagging scope agreed against a licence that does not carry it is a
conversation nobody enjoys having in week three.
What a tag is made of
A tag has an id, and the id is two parts separated by a colon:
namespace:name. The namespace names the dictionary the tag came from
and is normally one or two characters — n for Niagara,
hs for Haystack. A tag may also carry a value, which is where the
building name, the equipment reference or the location goes.
Mechanically, a direct tag on a component is a property holding a non-component value with the metaData flag set. That is worth knowing because it explains both why tagging is cheap and why an untidy tagging job is as durable as any other untidy property.
Three kinds, and only two of them scale
| Kind | Where it comes from | Use it when |
|---|---|---|
| Direct | Added deliberately from an installed dictionary, and stored on the component. | The normal case. Shared vocabulary, visible in the Direct Tags tab. |
| Implied | Not stored at all — produced by tag rules in a Smart Tag Dictionary, typically remapping properties the component already has onto the dictionary's naming. | Wherever the information is already in the station. Nothing to maintain and nothing to get out of step. |
| Ad hoc | Typed in the Add Tag dialog. A direct tag belonging to no dictionary. | Rarely. This is how a tagging project quietly turns into a second naming convention with no validation behind it. |
What a dictionary actually contains
A tag dictionary is more than a word list. It carries a unique namespace, tag definitions with their default values and validation rules, optional tag group definitions — standard groupings you can apply in one action — optional relation definitions, and, in a smart dictionary, the tag rules that generate implied tags.
Niagara 4.15 ships a Brick tag dictionary in the brick
palette, dropped into the TagDictionaryService over a Fox connection,
with two narrower alternates — BrickHasTagsOnly and
BrickSubclassesOnly. Brick models a building as a class hierarchy, so
which of the three you install decides how much of that ontology lands in the
station. Pick deliberately; retagging afterwards is the expensive direction.
Doing it to a whole station
Tagging point by point is how tagging projects die. The Batch Editor under
Program Service is the tool: Find Objects opens the
BQL Query Builder, you narrow the result set, remove what should not be there, and
Add Tag applies a tag — or a whole tag group — to everything
selected at once.
Do it at discovery time where you can. Associations are typically established when a device is discovered, registered and subscribed, and a tag added then costs nothing compared with a tag added to four thousand existing points.
What it buys
One thing, and it is worth the effort by itself: another piece of software can
discover what is in the station without knowing the naming convention the installer
used. Hierarchies, search, analytics and any external consumer stop depending on
whether somebody wrote SpaceTemp or ZnT in 2019.
Sources
Where this is written down
- Project Haystack, the ontology reference — The ontology the tag names come from, which is the reason a dictionary can be shared between estates at all
Related
Where this comes up in the work
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
Workbench tooling
Custom Workbench views and tools for repetitive Niagara work: bulk renaming and retagging, station audits, provisioning helpers and module inventories.
More notes
Other things worth writing down
One PX sheet for every AHU
The Px editor binds absolutely by default, which is why a graphic works for AHU-01 and nothing else. Relativised, one sheet serves the whole plant.
- PX graphics
- Standard sheets
- Reuse
Renaming and tagging points in bulk
Point names arrive from the field device and there is no standard. What to use to select, rename and tag in bulk — and what a rename quietly breaks.
- Bulk engineering
- Tagging
- Workbench
A navigation tree that builds itself
Hierarchies generate the nav tree from tags and NEQL queries instead of hand-placed nodes — and the cache hides your edits until you rebuild it.
- Hierarchies
- Tagging
- Station engineering
Next step
Tell us the version, the hardware, and what it has to do.
You will get a written scope and a fixed price against it. If the honest answer is that you do not need us, you will get that instead.