Note
Why a station polls too slowly
Nobody ships a station that is deliberately slow. It gets slow because every proxy point was created against one default tuning policy, and nothing ever asked which of them needed to be fast.
- Station engineering
- Performance
- BACnet
Where the speed is actually set
Each field-bus driver network carries a polling service — named Poll
Service or Poll Scheduler depending on the driver — and it
samples values at exactly three rates. The shipped intervals are:
| Rate | Default interval | What belongs here |
|---|---|---|
| Fast | 1 second | Points a control loop or an operator is watching change in real time. Very few of them. |
| Normal | 5 seconds | The working majority: temperatures, set points, status, anything on a graphic. |
| Slow | 30 seconds | Values that physically cannot move quickly, and anything only a history needs. |
These names mean nothing to the framework. Slow, Normal and Fast are labels on three configurable intervals, and no logic enforces any relationship between them. A station where Slow has been set faster than Normal is misconfigured and will not complain.
There is a fourth group that is easy to miss: Dibs Stack, which
handles pollables that transition into a subscribed state — the temporary
subscription created when somebody opens a graphic, for instance. It is why a
station can look responsive while an operator is watching and still be logging
stale data the rest of the day.
Which point gets which rate
This differs by driver, and it is the part that catches people moving between them.
- Under a BacnetNetwork, the poll frequency is a property of the tuning policy, and each proxy point is assigned a tuning policy. You do not set a rate on the point.
- Under most other drivers,
Poll Frequencyis a property of the point's own proxy extension, and of the device object where a device is pollable. It sits just below the address properties. - The NiagaraNetwork does not poll points at all. Station-to-station values arrive by subscription, so a slow Niagara Network is a different investigation entirely — look at its tuning policy's update times instead.
The single-policy trap
A driver's Tuning Policy Map ships with one default policy, and a station built without touching it has every point in the building on that one policy. Tridium's own documentation is unusually blunt about this: using only the single default policy, particularly with all property values at defaults, can lead to problems in many scenarios.
The fix is not clever. Duplicate the default policy three or four times, name the copies after what they are for, set their poll frequency, and assign points to them as the points are created. Done at engineering time it costs nothing. Done afterwards it is a bulk re-assignment across several thousand points, which is a different note.
Check Write On Start while you are in there. A tuning policy also
governs writes, and Write On Start decides whether the station pushes
its value out to the field device when it comes up. On plant that should not be
commanded by a station restart, that default matters more than any poll rate.
Measure before changing anything
The polling service publishes its own statistics, and they answer the question directly rather than by feel:
- Busy Time — the percentage of the time the station spent polling. This is the number that tells you whether the bus is saturated or the problem is somewhere else entirely.
- Average Poll — the average time spent in each poll.
- Total Polls, against the elapsed milliseconds.
Right-click the poll service and use Actions > Reset Statistics to
start a clean window before and after a change, so the comparison is between two
measurements rather than between a measurement and a memory.
One caveat on reading them: the BACnet driver polls on multiple threads — two per network port — and the statistics are the sum across all of them. There is no per-thread breakdown, so a busy figure on a station with several trunks tells you the station is busy, not which trunk is.
The order to work in
- Reset the statistics and watch Busy Time. If it is low, the polling is not your problem and re-rating points will not help.
- Count what is on Fast. Points that nobody reads at one second each are the usual cause, and moving them costs nothing.
- Build the policies, then re-assign. Three or four named policies covering fast, normal, slow and write-on-start behaviour.
- Re-measure. Same statistics, same reset, same window. A tuning change you did not measure is a preference.
Related
Where this comes up in the work
Station engineering
Niagara station and controller setup end to end: platform commissioning, TLS, users and roles, BACnet and Modbus, tagging, histories, alarms, backups.
Workbench tooling
Custom Workbench views and tools for repetitive Niagara work: bulk renaming and retagging, station audits, provisioning helpers and module inventories.
More notes
Other things worth writing down
Which Niagara version to stamp a module for
A module's declared dependency version is a floor, not a pin. Build against the newest SDK you have and stamp for the oldest station it has to load on.
- Module development
- Mixed estates
- Build tooling
What a station checks before loading a module
Niagara's three module verification modes, what each one demands of your certificate, and why the setting cannot be relaxed from the command line.
- Module signing
- Certificates
- Deployment
Pure Java, or it will not run on a JACE
A controller is an ARM host with a fraction of a server's memory. Native libraries, JNI and heavyweight dependencies do not survive the move from a PC.
- JACE