Note
Why a writable point ignores the value you set
A writable point does not have a value. It has sixteen inputs, two actions and a fallback, and what appears on Out is whichever of those won. Almost every "it will not hold" call is a fight between two of them.
- Station engineering
- BACnet
- Commissioning
The sixteen inputs and who owns them
Every BooleanWritable, NumericWritable,
EnumWritable and StringWritable carries inputs
In1 to In16, level 1 highest and level 16
lowest, plus a Fallback property below all of them. The level names
are borrowed from BACnet convention, and knowing them is the difference between
picking a level and guessing one:
| Level | Convention | Notes |
|---|---|---|
| 1 | Emergency, manual life safety | Not linkable. Issued as an action. |
| 2 | Automatic life safety | |
| 3, 4 | User defined | |
| 5 | Critical equipment control | |
| 6 | Minimum on/off | Reserved on a BooleanWritable for its built-in timers. |
| 7 | User defined | |
| 8 | Override, manual operator | Not linkable. Issued as an action. |
| 9 | Demand limiting | |
| 10 | User defined | |
| 11 | Temperature override | |
| 12, 13 | Stop and start optimisation | |
| 14 | Duty cycling | |
| 15 | Outside air optimisation | |
| 16 | Schedule | Where a schedule normally lands, and the reason it loses to everything. |
How the scan resolves
The priority scan runs on any input change, not on a timer. It looks for a
non-auto action at level 1, then takes the value of the highest valid input
from level 2 downwards, treating a non-auto action at level 8 as valid
when it reaches it. If nothing qualifies, Out takes
Fallback.
The word doing the work there is valid. An input is valid only if none of these status bits are set:
down— the device behind it is not answering.fault— the value arrived, but the source says it is wrong.disabled— somebody disabled the point or its parent.null— nothing has ever been written here.stale— no successful read inside the tuning policy's stale time.
That list is the whole diagnosis for most cases. A value sitting on
In10 that never reaches Out is not a priority problem;
it is a status problem at In10, or something valid above it.
Read the status, not the value. A point showing the wrong number
with {ok} is being beaten by a higher level. The same point showing
the wrong number in override colour is being held by an action, and no amount of
re-linking will move it.
The linking rules
- One link per level. A second link to the same input is refused.
- Levels 1 and 8 cannot be linked at all, because they belong to the emergency and override actions.
- Level 6 cannot be linked on a BooleanWritable, because the minimum on/off timers own it.
Both of those last two are a change from the AX-era scheme, where a writable
object took a single priorityArray input that several outputs could
be linked into, including at duplicate levels and at levels also used by commands.
Logic carried across from an AX station will not link the way it used to, and the
usual workaround is a free user-defined level — 3, 4, 7 or 10 — rather than trying
to reproduce the old arrangement.
Fallback is a value an operator can change
Fallback is not a safety constant. Every writable point ships with a
Set action that writes directly to it, and that action is available
to an operator-level user by default. A setpoint that drifts overnight with nobody
admitting to it is usually this.
Two things follow. If the point should fall back to nothing rather than to a
number, set Fallback to null — which the property sheet accepts and
the Set action does not — and then set the Hidden config flag on the
Set slot from the slot sheet, or the next user puts a number back.
The other direction is the useful one. Proxy points are always read-only points,
but they inherit the actions of the source point, so a NumericWritable exported
over a NiagaraNetwork gives an operator a working setpoint through a
SetPoint widget on a graphic without a second writable point being
created anywhere. The kitControl constants behave the same way, except that they
have no priority inputs at all and Set simply writes their output.
The two overrides behave differently
They look like a pair in the right-click menu and they are not.
- A manual override at level 8 prompts for a duration. Permanent is first in the list, so it is what gets clicked; the timed options and a custom hours/minutes/seconds entry are underneath it. When a timed override expires the scan returns to automatic control on its own. A maximum duration can be imposed through the point's facets.
- An emergency override at level 1 has no duration at all. It
holds until somebody right-clicks the point and chooses
Auto. There is no expiry to wait for, and nothing in the station will clear it.
Both show override status, violet by default. On handover, the emergency level is worth restricting: by default every action except the emergency ones is available to an operator-level user, and that split is set with config flags on the action slots — editable across many points at once in the batch editor.
BACnet priority is a different scheme
This is the one that costs a day. Niagara's sixteen levels are patterned on
BACnet's, but there is no linkage between them. The station's priority scheme is
station-centric, and writing to In8 of a BACnet proxy point is not the
same act as writing at BACnet priority 8 in the device.
When a write does not arrive, the proxy extension says so and people do not look.
Write Status reports read only, writable or
the failure text, and the classic failure is making a NumericWritable for the
presentValue of an Analog_Input, which comes back as
Property: Write Access Denied. A genuine BACnet error arrives in the
device's own words, as error class and error code separated by a colon.
To see what the device thinks its priority array holds, add a boolean facet named
priorityArray to the point's facets — not the device facets
on the proxy extension. The status then carries bac=X, with X the
level in the device that is currently winning. The same mechanism polls
statusFlags, which merge into the point's status, plus
eventState and reliability, which report as
state= and reliability=. Without them the driver polls
one property and an object in alarm looks perfectly healthy.
Note also Property Array Index. It is -1 for any property
that is not an array, which includes presentValue. Set it to a number
only when you genuinely mean one element — proxying level 7 of a binary output's
priority array, for instance.
Exposing a writable the other way
When the station is the server rather than the client, the failure moves to
permissions. The BACnet driver serves every exported object read-only through a
station user called BACnet, which it creates itself at startup with
no permissions at all. An external system writing to an exported
NumericWritable, or invoking an action on an exported BooleanWritable, needs that
user given write permission on the category the points live in — and a non-blank
password, since it now holds write rights. The same permissions govern writes to
exported files and histories.
The order to work in
- Open the property sheet, not the graphic. All sixteen inputs, their statuses and the fallback are on one page, and the answer is normally visible without changing anything.
- Find the winner. Highest valid input, or an action at 1 or 8, or fallback. If it is an action, nothing else matters until it is auto'ed.
- Check the loser's status. If your value is not winning and nothing above it is valid, it is one of the five bits — most often
nullon a link that was never made. - Only then look at BACnet. Write Status names the failure, and a
priorityArrayfacet shows whose value the device is actually holding.
Whether the station writes to that array at all depends on the object type the
gateway exposes, and that branch is readable in the driver:
bacnet-priority-scan prints
which types are assumed prioritized, which are probed once, and what a failed probe
does to the point.
Sources
Where this is written down
- ANSI/ASHRAE Standard 135-2024, BACnet, free read-only edition — Niagara's sixteen priority levels are the standard's priority array; the mapping this note describes only means anything against that definition
Related
Where this comes up in the work
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
Operator graphics
Niagara operator screens built once and reused: standard PX plant sheets bound by relative ORD, bajaux web widgets and dashboards, and a written standard.
More notes
Other things worth writing down
Why a station polls too slowly
Slow, Normal and Fast are three numbers you choose, and one default tuning policy applied to every point is the usual reason a station feels sluggish.
- Station engineering
- Performance
- BACnet
BACnet MS/TP on a JACE
Baud, MAC address, Max Master and Max Info Frames. Four settings on one Link component decide whether an RS-485 trunk works, crawls or drops the token.
- BACnet
- MS/TP
- Commissioning
What a BACnet discovery sweep actually tells you
Who-Is stops at the subnet, I-Am carries no device name, and an object list from a device that cannot segment has to be read one index at a time.
- BACnet
- Discovery
- Commissioning