Note
Platform or station: two connections, two sets of logins
Half the confusion in a first Niagara job comes from one fact nobody says out loud: the platform and the station are separate programs, and almost nothing crosses between them.
- Platform
- Station engineering
- Workbench
Two processes, two virtual machines
The platform daemon, niagarad, is pre-installed on every controller
from the factory and starts whenever the hardware boots. It is Java, running in
its own Hotspot VM, and it runs whether or not there is a station — a brand-new
controller with no station installed is still fully manageable. The station, when
one exists, runs in a second and separate VM that the daemon starts and
stops.
Which is why there are two kinds of connection. A platform connection is Workbench talking to the daemon, on HTTPS 5011 where TLS is available and 3011 where it is not. A station connection is Workbench, or another station, talking to the station over Fox. They authenticate differently, they show different views, and one being up tells you nothing about the other.
A platform connection needs Workbench. There is no browser
equivalent — no amount of WebService configuration will expose Software Manager or
the Station Copier to a browser. The one indirect route is a Supervisor station
reaching a remote platform through its ProvisioningService, which is
exactly why provisioning exists.
Two sets of credentials, and neither manages the other
Platform users live in the daemon. There can be up to twenty, every one of them a full administrator able to create more, and there is no way to hand out a restricted one. Station users live in the station database, with roles, categories and permissions, and can be as narrow as you like.
Deleting a station user does not affect platform access. Losing the platform password does not lock you out of the station, and vice versa. On a site where somebody has left, both lists need checking, and the platform list is the one that usually gets forgotten because it is only visible over a platform connection in the first place.
PlatformServices: the station's window onto the platform
There is one deliberate hole in the wall. Every running station has a
PlatformServices container under Config → Services, reachable
over an ordinary Fox connection by any station user with admin permission on
Services — no platform connection involved. It exposes a subset of the platform
views, and a few settings that exist nowhere else.
| Service | Where | What it gives you |
|---|---|---|
| TcpIpPlatformService | PC and controller | the same addressing as the platform's TCP/IP view |
| LicensePlatformService | PC and controller | the same licences as License Manager |
| CertManagerService | PC and controller | key store, trust store and allowed-host exceptions |
| SyslogPlatformService | PC and controller | ships Niagara log messages to a remote syslog server |
| SerialPortService | controller only | which serial ports the host actually has |
| NtpPlatformService | controller only | the QNX NTP daemon and its list of time servers |
| DataRecoveryService | controller only | the static RAM buffers behind battery-less operation |
| HardwareScanService | controller only | a labelled diagram of the ports on this model, if
platHwScan is installed |
Two things about this container catch people out. It is built dynamically when the
station starts, so it does not exist in an offline station — open the .bog in
Workbench and there is nothing to look at. And its settings are not stored
in the station database: they go to platform.bog or to the operating
system, which means they survive the station being replaced, and a station backup
does not carry them.
Be careful who gets admin on Services. This is the part of the station that holds host licences and IP settings, and the right-click menu on PlatformServices includes Restart Station. A permission model that is careful about setpoints and casual about Services has the wrong shape.
Where the files actually live
A controller has exactly two homes, and both are visible under Platform → Remote File System.
| Home | Alias | ORD | Path | Contents |
|---|---|---|---|---|
| System Home | niagara_home | ! |
/opt/niagara | the installed software; read-only |
| daemon User Home | niagara_user_home | ~ |
/home/niagara | configuration and the installed station |
Inside the station folder there is a second split, and this one changed at N4. The
station root is the protected station home, which only core
Niagara modules may touch: config.bog and its timestamped backups
sit there, along with alarm, history,
dataRecovery, provisioningNiagara and the virtual driver
folder. The shared sub-folder is the ordinary one, writable by any
module, and it holds px, images, nav and
everything else a graphic refers to.
The consequence for anyone writing a module: the ^ ORD, which in AX
pointed at the station root, now points at shared. The Java Security
Manager enforces it, so a module that writes to the station root does not misbehave
quietly — it fails. On the other hand N4 no longer needs the file blacklists AX
relied on, because the boundary is structural.
The Application Director is the platform's view of the station
One platform view is worth learning properly. On a controller the Application
Director lists exactly one station — a Windows host may list several — and its
Details column is the fastest answer to "why can I not reach it": fox=
and foxs= for Workbench, http= and https=
for browsers, foxwss= for Fox over WebSocket. Each reads
n/a when that protocol is disabled or the station is not running, and
a station with http=n/a is not a network problem.
Two properties decide what happens without you. Auto-Start starts
the station after the daemon does, which covers every reboot, every dist file
installation, every TCP/IP change and every module upgrade — all of which restart
the station whether you asked or not. Restart on Failure has the
daemon restart a station that exits with an error, such as one the engine watchdog
killed for a deadlock. It gives up after three automatic restarts in ten minutes,
leaving the station failed rather than flapping; the count is the
Failure Reboot Limit property on the station's PlatformService.
Note that this view does not behave like the rest of Workbench: there is no Save
button, and every checkbox and button applies the moment you click it. Stop shuts
the station down cleanly, saving config.bog and history. Kill does not
— it terminates the process, and whatever was unsaved is gone. Between the two,
Verify Software is the quiet one worth using: it parses
config.bog and platform.bog and tells you which modules
the station references but the host does not have.
Move stations with the Station Copier, not the file system
It is tempting to drag a station folder across with the file transfer client, and it produces a station nobody can log into. The Station Copier transcodes user passwords for the target host as part of the copy; a raw file copy does not, so the users arrive unusable. It also checks the target for the modules the station depends on before it starts, and refuses rather than installing something that cannot run.
Module signatures are checked on the way in too. Warnings on a dependency raise a Signature Warning window you can accept; a signature error fails the copy outright. That is the same gate a module faces at install time, arriving at the least convenient moment — which is an argument for getting signing right long before the station moves.
Related
Where this comes up in the work
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
More notes
Other things worth writing down
What a station checks before loading a module
Niagara's four verification-mode values, what each demands of your certificate, and the permissions that force a signature check even in low mode.
- Module signing
- Certificates
- Deployment
Roles, categories and the grid between them
A user authenticates and every view is empty. Permissions are a grid of category against level, held by a role — read it in that order to find the gap.
- Station security
- Permissions
- Commissioning
Commissioning a JACE-8000 without locking yourself out
The factory address, the passphrase with no recovery path, and the account you are made to delete — the Niagara 4 steps that strand a new controller.
- JACE
- Commissioning
- Deployment
Next step