Note
Why an alarm never reached anybody
An alarm that nobody received is rarely an alarm that was never raised. It was raised, stored, and routed nowhere — because routing is a link somebody has to draw.
- Alarms
- Station engineering
- Commissioning
Three objects, not one
Niagara splits alarming into three things that are configured independently, and the split is the reason alarms go quiet.
- An alarm extension on a point decides when a condition is an alarm.
- An alarm class groups alarms that share handling — acknowledgement, priority, escalation — and is the thing that routes.
- An alarm recipient delivers: to a console, to another station, to email, to an on-call rota.
Break the chain at any point and the station carries on perfectly. The extension still fires, the alarm still lands in the database, the counts on the alarm class still increment. It simply never becomes anybody's problem.
Choosing the extension that matches the failure
There are more extension types than most stations use, and the common reflex — an out-of-range extension on everything — misses whole categories of fault.
| Extension | What it catches |
|---|---|
| Out Of Range | Numeric high and low limits with a deadband. The default choice, and the right one for a measured value with absolute limits. |
| Float Limit | Limits expressed relative to a setpoint rather than as absolutes. This is the one people want when they say "alarm if it cannot hold setpoint" and reach for Out Of Range instead. |
| Status | Fires on any combination of status flags — fault, down, stale, overridden, null. Applies to any point type. This is how you find out a sensor died rather than reading zero degrees forever. |
| Command Failure | Boolean or enum. Compares the commanded value against a linked
feedbackValue and alarms if they disagree for longer than the
time delay. The only honest way to know a damper actually moved. |
| Change Of State / Value | Boolean, enum, numeric and string variants, for conditions defined by a set of values rather than a range. The boolean and enum versions implement the BACnet change-of-state algorithm. |
| Elapsed Active Time Change Of State Count |
In the kitControl palette. Alarm on accumulated runtime or on
accumulated starts — maintenance alarms rather than fault alarms. Both
reference a totaliser extension under the same point. |
Every extension carries two algorithms. An offnormal algorithm and a fault algorithm sit inside each one. The fault algorithm's default implementation raises nothing, so a point can be in fault without generating a fault alarm unless you configure it or add a status extension.
What the alarm class actually controls
The class is where acknowledgement, priority and escalation live. Priority runs 0 to 255 with a default of 255, which is the lowest — so a station where nobody set priorities has every alarm at the bottom of the queue, and the colour coding operators rely on is meaningless.
The class also carries read-only counters worth looking at during commissioning: total alarm count, open alarm count, in-alarm count, unacknowledged count, and the time of the last alarm. If those numbers are climbing and nobody is receiving anything, the detection half is working and the routing half is not. That single observation cuts the diagnosis in half.
What the station does between the class and the recipient is readable in the shipped
jars, and it is less of a fan-out than it looks:
alarm-route-scan prints the single
queue every alarm route in the station is drained through, the coalesce rule that
collapses two routes of one record by default whatever their states are, and the
invocation that reports success for the copy it discarded.
Escalation, and why it needs somewhere to go
Three escalation levels re-route an alarm that stays unacknowledged. Each has an enable flag — off out of the box — and a delay, which starts at five, fifteen and thirty minutes and will not go below one, two and three. An alarm that survives all three has been offered to as many as four recipients including the original; acknowledgement at any level stops the chain.
Those defaults are the trap. The levels sit in the property sheet with delays already filled in, which reads as configured, and a station nobody has touched escalates nothing: an alarm that is never acknowledged is simply never re-routed. Enabling a level and linking no recipient to it arrives at the same place by the other road. Both are worth checking before anyone signs the job off.
Recipients, and one that does not exist on a controller
Recipients are linked from the alarm class's alarm topic to the recipient's Alarm action. Each can be restricted by time of day, by day of week, and to specific transitions — so a recipient that is silent at 3am may be working exactly as configured.
- Console moves alarms between the alarm history and the alarm console, and updates the history when they are acknowledged.
- Station forwards to a remote station, which is how a controller gets alarms to a Supervisor.
- Email, SMS and on-call deliver to people rather than to software.
- Printer and line printer require a station running on Windows. On a QNX controller they are not an option, which is worth knowing before it appears in a specification.
The delivering half fails differently, and quietly.
alarm-recipient-scan reads what
the base class does with a recipient's own result: returning false from
sendAlarm drops that alarm with no fault status, no failure cause and
nothing logged, while throwing is the only route into the recovery machinery —
which is persistent and retries every 15 seconds out of the box.
Tridium's own advice is to use more than one class. One alarm class routing to a console recipient and a station recipient; a separate class routing to email. Trying to make a single class serve both leaves you filtering at the recipient for something the class should have separated.
Station to station: the link everybody forgets
Getting alarms from a controller to a Supervisor needs configuration at both ends.
In the sending station, an alarm class and a station recipient in the
AlarmService, linked together. The two stations do not have to use the
same class names, though matching them is one legitimate approach; the receiving
side can also collapse everything onto one local class, or use a prepend or append
naming scheme to map classes by name.
In the receiving station, link the alarm class to the alarm console. Remote alarms arrive, are stored, and do not appear in any console unless the associated alarm class is linked to the console component. This is the single most common reason a Supervisor shows nothing while the controllers are alarming correctly — and because the data is present in the database, it looks like a display bug rather than a missing link.
Reassigning classes without opening every point
Alarm extensions are scattered across hundreds of points, so changing a class point
by point is not viable on a real station. The AlarmService has an
Alarm Ext Manager view that lists every alarm extension in the
station; select any number of them, right-click, and set the alarm class in one
operation.
For alarms arriving from subsystems with their own class names, alarm class mapping lets you associate imported classes with local definitions so they display, sort and sound consistently instead of forming a separate vocabulary in the console.
A commissioning check that takes ten minutes
- Force one alarm of each class and confirm it arrives at every recipient that class is meant to reach. Not one alarm — one per class.
- Check the class counters afterwards. Rising counts with no delivery is a routing fault; flat counts is a detection fault.
- Enable level 1 escalation, then leave an alarm unacknowledged past its delay and confirm it goes somewhere. The enable flag is off until somebody turns it on.
- Confirm the Supervisor console shows it, not just the Supervisor database.
- Check who can clear the alarm database. The maintenance view can delete records outright; operators should have the read-only alarm database view instead.
- Write alarm instructions on the points that matter, so the operator receiving the alarm at 3am is told what to do about it.
Sources
Where this is written down
- ANSI/ASHRAE Standard 135-2024, BACnet, free read-only edition — The change-of-state algorithm the boolean and enum extensions implement is the standard's own intrinsic reporting one, not a vendor invention
Related
Where this comes up in the work
Station engineering
JACE controller and Niagara station setup end to end: platform commissioning, TLS, users, roles, BACnet and Modbus, tagging, histories, alarms, backups.
Operator graphics
Niagara operator screens built once and reused: standard PX plant sheets bound by relative ORD, bajaux web widgets and dashboards, and a written standard.
More notes
Other things worth writing down
Niagara schedules: special events and master copies
Special event priority is list order, a partly-filled special event falls back to the weekly schedule, and an imported schedule cannot be edited locally.
- Scheduling
- Station engineering
- Commissioning
Why a writable point ignores the value you set
Sixteen priority inputs, two of them reserved for right-click actions, a fallback underneath, and a BACnet scheme wired to none of it.
- Station engineering
- BACnet
- Commissioning
Roles, categories and the grid between them
A user authenticates and every view is empty. Permissions are a grid of category against level, held by a role — read it in that order to find the gap.
- Station security
- Permissions
- Commissioning
Next step
Tell us the version, the hardware, and what it has to do.
You will get a written scope back, and a clear answer on whether we are the right team for it. If the honest answer is that you do not need us, you will get that instead.