Conversion links: what a mismatched wire really does

Drag a wire between two slots of different types and it just works, which is the problem: a converter was inserted, it has settings you did not choose, and null does not behave the way you expect.

  • Station engineering
  • Wire sheet
  • Workbench

Written

The wire that converts itself

Since AX-3.6, linking two slots of dissimilar data types produces a conversion link automatically. Before that the same job needed a Program object, which is why older stations are full of them. The link is not a plain wire: it carries a child Converter component whose type is chosen for you from the pair of types involved, and some of those converters have properties.

To see one, right-click the wire on the wire sheet and choose Edit Link. If the link shows as a knob rather than a wire — which is what happens when the other end is off-sheet — open the component's link sheet and double-click the row. The Converter appears as an expandable node inside the Edit dialog.

This is worth doing deliberately rather than never. A conversion link is not wrong, it is just silent, and the defaults are only right some of the time.

Not every pair is allowed

The conversion matrix is wide but not complete, and the holes are the useful part to remember. A link Niagara will not make is one you have to solve with a component, so knowing the gaps saves a wire-sheet argument.

TypeWhat it will not do
frozenEnum nothing can convert into it — its whole row of the matrix is blank. It converts outwards to everything except ord and the time types
ord exchanges only with string and statusString, both directions, and with no validation in either
boolean no conversion either way with any time type
statusEnum, dynamicEnum reachable from booleans, numbers and other enums, but never from a string or a statusString
time arrives only from the plain number types and absTime — statusNumeric cannot reach it, though it can reach absTime and relTime
relTime arrives from numbers and statusNumeric; leaves as numbers, statusNumeric or a string — never a boolean or an enum

Booleans, numbers, and the False Value property

The everyday case is a boolean driving something numeric. A statusBoolean linked to a statusNumeric gives 1 for active and 0 for inactive, and that is usually what you wanted. Where the target is a plain number type, the Converter carries True Value and False Value properties, defaulting to 1 and 0 — and those exist because the defaults are frequently useless. Driving a MultiVibrator's Duty Cycle, which runs 0 to 100, means editing them to something like 75 and 25 rather than adding arithmetic downstream.

Going the other way, a number linked to a boolean uses a False Value with a default of 0: anything else is true. Worth saying out loud that this includes negative numbers, so a sensor reading -4 is true, not false. If the meaningful off-state is some other value, set False Value to it.

Number to number is unremarkable except at the edges, where the result clamps rather than wrapping. A double of 2147484000 into an integer slot lands on 2147483647, the integer maximum, with nothing to indicate it happened.

Strings are where it goes wrong

String conversions are the ones to be suspicious of, because each failure mode is different and none of them is loud.

LinkWhat bad input produces
string → double or float nan — anything that is not a plain decimal number, blank included
string → long or integer 0, or the last non-zero value, if there are any extra characters
string → statusNumeric a fault on the target, with the value left unchanged
string → boolean true, for everything except the False Value string (default "false", case insensitive) — and a blank string is true
string → absTime null, unless the string is ISO-formatted (yyyy-mm-ddThh:mm:ss.mmm±hh:mm)
string → ord whatever you gave it — there is no ORD validation at all

The pattern to notice is that the three numeric targets fail three different ways: one gives a not-a-number, one silently holds its last value, one raises a fault. Only the statusNumeric case is visible on a graphic. If a string from a third-party integration is feeding logic, that is the target type to prefer, purely because it tells you when the parse failed.

Null is not zero

Every status type can be null, and what a conversion does with null is decided per target type rather than uniformly. This is the trap that produces plant running on stale values after a device goes offline.

TargetOn a null source
double, floatbecomes nan
long, integerunchanged — keeps the last value
stringunchanged — keeps the last text
booleanunchanged
statusBoolean, statusNumeric, statusEnum, statusString becomes null, so the status propagates
absTimebecomes null
relTimeunchanged

Convert between status types wherever the value matters. The simple types have nowhere to put a status, so the only honest thing a converter can do is leave the old value in place — which downstream logic cannot distinguish from a live reading. A chain that drops to boolean or integer halfway along has thrown away the fault flag for good.

Times are milliseconds, from three different origins

All the time conversions are millisecond arithmetic; what differs is where zero sits. To relTime, milliseconds count from 0, so 4800000 is 1h 20m and a negative value is allowed. To time, they count from midnight, so 900000 is 00:15. To absTime, they count from the Java epoch, so 1296509138929 lands in January 2011.

The reverse directions mirror that: relTime and time to a number give milliseconds from their own origin, absTime gives milliseconds since the epoch. Two special cases are handy — absTime to time keeps the time portion and drops the date, and time to absTime takes today's date, which is the shortest route from a schedule-style time to a real timestamp.

Formatting on the way to a string

Any conversion whose target is a string or statusString has a Format property, and its default depends on the source.

From a number it is blank, meaning every digit, unformatted. Fill it in with # for digits, 0 for forced leading or trailing zeros, and comma or period as separators: ###,###.### turns 123456.789 into 123,456.789, ###,## turns it into 123456.79, and 00000.000 turns 123.78 into 000123.780.

From a boolean the default is %.%, which is BFormat — so static text can be wrapped around the value, and a format of Enabled: %.% produces exactly that. From absTime the default is YYYY-MM-DDTHH:mm:ssZ and from time it is HH:mm:ssZ; both accept the usual patterns, so HH:mm a gives 3:31 PM and MM-DD-YYYY HH:mm reorders the date.

Enums are the pleasant surprise here. A statusEnum linked to a string gives the tag rather than the ordinal — "Occupied", not "1" — which is usually what a graphic or an alarm message wanted. Link it to a number and you get the ordinal instead.

Conversion links are otherwise a leave-alone feature, with one documented exception: linking out of the dynamically created components under a station's PlatformServices. Those components are built at runtime rather than stored, so a link that identifies its source by Handle points at something that will not exist the same way next start. Open the link and change Source Ord from Handle to Slot, and it survives.

A tool that copies components and rebuilds their links in bulk has to get that same distinction right. We read one in public, found two places where it did not, and the author implemented both: a code reading the author then implemented.